From: Gerhard Hoffmann
Newsgroups: sci.electronics.design
Subject: Re: Grand Apagon - Electricity (not) in Spain
Date: Wed, 30 Apr 2025 14:11:10 +0200
Message-ID:
References:
<1rbln2a.1frrgzg19gl8fgN%liz@poppyrecords.invalid.invalid>
MIME-Version: 1.0
Content-Type: text/plain; charset=UTF-8; format=flowed
Content-Transfer-Encoding: 8bit
Injection-Date: Wed, 30 Apr 2025 12:11:10 -0000 (UTC)
Injection-Info: solani.org;
logging-data="72603"; mail-complaints-to="abuse@news.solani.org"
User-Agent: Mozilla Thunderbird
Cancel-Lock: sha1:LKfWhLm84dW9GbczWL85NZq81bI=
Content-Language: en-US
X-User-ID: eJwFwQEBACAIA7BKB/yROqj0j+DGkOnkErU4nNhPbwFefTUyv0A4mW01MEbA6iaqPPvY/v2BD6o=
In-Reply-To:
Bytes: 2509
Lines: 32
Am 30.04.25 um 12:41 schrieb Carlos E.R.:
> On 2025-04-30 11:59, Liz Tuddenham wrote:
>> Bill Sloman wrote:
>> The grid frequency begins to fall so energy from the moving parts is
>> converted to electrical power which is fed into the grid to increase.
>> the frequency. This results in a loss of stored mechanical energy which
>> causes the turbine to begin slowing down - which is detected by the
>> control system and used to feed more water/gas/steam into the turbine so
>> its speed is returned to normal.
>
> I understand that the turbine doesn't actually slow down, because the
> generator starts working as a synchronous motor drawing energy from the
> network instead; this is detected by the control system and feeds more
> water/gas/steam, etc.
>
> As long as the network keeps the frequency.
Actually, the grid frequency is a bit elastic.
We had that in the European grid some years ago, when
some Balkanese enclaves / exclaves did not care much
about cos_phi correction and the grid drifted slooowly
to a lower frequency. No bad consequences other than some
wall clocks were a few minutes late after a week or two.
I found that easy to measure with a time interval counter.
(ps resolution in a second elapsed time)
<
https://www.flickr.com/photos/137684711@N07/38870750440/in/datetaken/lightbox/
>
Cheers, Gerhard